0.6/1kV 90°C MICA TAPE CROSS-LINKED POLYETHYLENE INSULATED POLYOLEFIN SHEATHED FIRE RESISTANT FLAME RETARDANT WITH LOW SMOKE AND ZERO HALOGEN SHIELED CONTROL CABLE
CONDUCTOR
Stranded annealed copper
FIRE BARRIER TAPE
Mica tape
INSULATION
Cross-Linked polyethylene (XLPE)
CORE IDENTIFICATION
2 Cores : Blue and Brown 3 Cores : Brown, Black and Grey 4 Cores : Blue, Brown, Black and Grey More than 4 Cores : Black with marking numbers, colored white, printed continuously throungout the whole length of insulated wires for the propose of core indentification
INNER SHEATH
Black Low smoke and zero halogen flame retardant polyolefin (ST8)
SHIELD
Laminated aluminium boned with polyester tape and drain wire
OUTER SHEATH
Orange Low smoke and zero halogen flame retardant polyolefin (ST8)
CLASSIFICATION
Maximum conductor temperature 90°C Circuit voltage not exceeding 1,200 Volts
RATED VOLTAGE
600 Volts between Line to Earth 1,000 Volts between Line to Line
TESTING VOLTAGE
3,500 V
REFERENCE STANDARD
Construction : IEC 60502-1 Circuit integrity : BS 6387 Category C, W, Z Flame retardant : BS EN 60332-1-2 BS EN IEC 60332-3-22 Category A BS EN IEC 60332-3-23 Category B BS EN IEC 60332-3-24 Category C Acid gas emission : BS EN 60754-1, BS EN 60754-2 Smoke emission : BS EN 61034-2
APPLICATION
For Fixed installation in electrical cabinet, conduit, trench and tray which provide flame retardant, low smoked and corrosive gases properties and main circuit integrity under fire