0.6/1KV-FRLH-IE

600/1000 V 90°C CROSS-LINKED POLYETHYLENE INSULATED FLAME RETARDANT WITH LOW SMOKE AND ZERO HALOGEN POWER CABLE

CONDUCTOR

Non-Compacted and compacted round annealed copper

INSULATION


Flame retardant Low smoke and halogen free Cross-linked polyethylene (LSHF-XLPE:EI5)

CORE IDENTIFICATION

Single-Cores: Black or Orange

CLASSIFICATION

Maximum conductor temperature 90°C
Circuit voltage not exceeding 1,200 Volts

RATED VOLTAGE

600 Volts between Line to Earth
1,000 Volts between Line to Line

TESTING VOLTAGE

3,500 V

REFERENCE STANDARD

Construction : BS EN 50525-3-41
Flame retardant : BS EN 60332-1-2
BS EN IEC 60332-3-22 Category A
BS EN IEC 60332-3-23 Category B
BS EN IEC 60332-3-24 Category C
Acid gas emission : BS EN 60754-1, BS EN 60754-2
Smoke emission : BS EN 61034-2
Non-toxic gases : Defence standard 02-713

APPLICATION


For Fixed installation in electrical cabinet, conduit and wireway which provide flame retardant, low smoked and non toxic emission under fire